SCOPE OF WORK
Date: November 6, 2019
Building: Joseph P. Addabbo Federal Building
Project Title: LAN Cables and Electrical Outlets for Adobe Connect Project
*Walk through: NOVEMBER 12TH, 2019*
Please email: daisy.tamberino@gsa.gov & joseph.virga@gsa.gov to confirm your attendance at the walk through.
Proposals due: 12/2/19 12PM
The purpose of this project is to install CAT 6 LAN cables and electrical outlets in the 3rd Floor Jamaica District Office IVT room and the 2nd Floor Office of Hearings Operation IVT room. Both offices are located inside of the Joseph P. Addabbo Federal Building. This work is required in preparation for the national rollout of the Adobe Connect (AC) Interactive Video Teletraining (IVT) Modernization.
The contractor shall be responsible for providing a minimum Category 6 (as defined by the TIA/EIA 568 Standard) compliant data channel from the patch panel in the DCR (Data Communications Room).
The contractor shall punch down at the patch paneland the patch panel shall be labeled by the contractor. The cable itself shall also be labeled accordingly. Labeling for the patch panel must be machine generated, hand written labels are unacceptable.
The contractor shall leave a minimum of five feet of slack in the DCR.
The contractor is responsible for attaching all connectors to the LAN cables.
The contractor shall certify compliance by testingand the results compared to the TIA/EIA 568 standard and requirements set forthin this document for the appropriate cable type.
NONE of the cable runs shall be on the ceiling, tiles or grid. ALL cables run shall be supported using the existing cable trays or using J-hooks. The contractor shall terminate all cables appropriately terminated and subsequently tested and certified. A formal testing report shall be provided to the Social Security Administration.
LAN CABLING:
2nd Floor: Run (2) LAN cables (minimum Category 6) from Office of Hearings Operations (OHO) LAN closet to the OHO IVT Room (Total length of each run is approximately 250 feet).
(2) wall plates with female connectors are to be installed. Locations along wall areto be determined. Wall plates and the patch panel shall be labeled.
3rd Floor: Run (15) LAN cables (minimum Category 6) from Jamaica District Office LAN closet to the Jamaica District Office IVT Room. (Total length of each run is approximately 150 feet).
The contractor shall purchase and install (15) new individual boxes with female connectors are to be installed. The exact box locations at the desks will be determined. Wire molding shall be installed to hide wires coming down from the ceiling along the window mullions. Floor wire covers to be provided at the floor to cover cabling running along the carpet. Wire molding color to match window frames. All boxes and the patch panel shall be labeled.
The contractor shall purchase and install (1) new 45 port patch panel
ELECTRICAL OUTLETS:
3RD FLOOR DISTRCT OFFICE:
·
·
·
·
·
·
·
·
III . DATA REQUIREMENTS
ABBREVIATIONS AND DEFINITION OF TERMS:
DCR – Data Communications Room
EIA – Electronics Industry Association
FIPS PUB 94 - Federal Information Processing Standard, Publication 94
IG – Isolated Ground
NFPA – National Fire ProtectionAssociation
NEC – National Electric Code
STP-- Shielded, twisted pair cable generally meaning IBM Type 1 or Type 1A
TIA -- Telecommunications Industry Association
UTP -- Unshielded twisted pair cable
REFERENCES:
Conformance to the latest revision ofthe following is required under this specification.
A. FCC Regulations:
1. Part 15- Radio FrequencyDevices& Radiation Limits
2. Part 68- Connection of Terminal Equipment to the Telephone Network
B. FIPS PUB 94 - Federal Information Processing Standard 94, See FTR
C. FTR 1090-1997 - The National Communication System is now responsible for issuing and maintaining information relating to the Federal Government’s communications standards. FIPS PUBs have been superseded by a system of Federal Telecommunications Recommendations. Specifically, FTR 1090-1997, Commercial Building Telecommunications Cabling Standard, outlines requirements for the installation of structured cablingsystems in Federal buildings.
D. NEC - The National Electric Code (NEC) is published by the National Fire Protection Association (NFPA) and is part of most building codes. Compliance with the latest edition of this code is mandatory for electrical installation to safeguard persons and property from hazards arising from the use of electricity. Some local building codes may also have additional requirements.
E. National, State, Local and any other binding building and fire codes.
F. TIA/EIA 568 – Commercial Building Telecommunications Cabling Standard
G. TIA/EIA 569 - Commercial Building Standard for Telecommunications Pathways and Spaces.
H. TIA/EIA 606 - Administration Standard for the Telecommunications Infrastructure of Commercial Buildings.
I. Underwriter’s Laboratories (UL): Applicable listing and ratings
General:
1. Provide a continuous single cable, homogeneous in nature for every cable run. Splices are not permitted.
Manufacturers:
Manufacturers are shown below as an indication of acceptable product quality. “Or equal” substitutes will be considered upon submission.
1. AMP, Belden, Berk-Tek, Chatsworth, Fibertron, JDI, Leveton, Lucent Technology, Mohawk, Nordx/CDT, Ortronics, Panduit, Suttle, TheSiemon Company.
Cable
Provide horizontal minimum Category 6unshielded twisted pair (UTP) cable or higher meeting the following requirements:
a. Provide cable suitable for indoor installation.
b. Provide cable with 4 twisted pairs of insulated copper conductors per cable, 24 AWG solid copper, fully insulated with retardant low-smoke thermoplastic material, plenum NEC CMP rated, and UL listed as such.
c. Color code twisted pairs individually, within color coded bundles, to industry standards (ANSI/ICEA Publication S-80-576, and EIA-230).
d. Comply with appropriate TIA/EIA-568 performance requirements.
Connectors
1. Fiber- Backbone cabling multimode fiber optic connectors shall be type LC or as determined by SSA.
2.Copper- Category 6, 8-pin modular connectors, T568-A wired.
CITE: https://www.fbo.gov/notices/844b6162b4b2d8bb05f96b24c9a9a6d0
SET-ASIDE: Total Small Business